Recently Updated Pages
Access Flooring System
Underfloor concrete shall be cleaned and sealed after all major underfloor work has been done, in...
Airborne Particles
Non-conductive airborne particles can be minimized by: Doing all unpacking, cutting, and drill...
Access Control Systems
Access control shall be provided at all entrances to the data center and all entrances to the com...
Fire-Rated Construction
Walls separating computer room, electrical rooms, battery rooms, mechanical rooms, and separate T...
Computer Room Wall Construction
The perimeter walls to the computer room shall be slab-to-slab and the perimeter walls of the com...
Floor Slab
Floor slabs shall be as per the calculations of the structural engineer, but no less than a floor...
Equipment Staging and Storage
Datacenter should have separate rooms to store arriving equipment and prepared in a room away fro...
Circulation
Clear pathways allowing for the movement of racks, processing, and support equipment shall be pro...
Fire Suppression Room
A separate room shall be provided for the pre action sprinkler control valve system for class 4 d...
Electrical Room and UPS Room
A separate room shall be provided to contain the data center associated electrical equipment, inc...
Mechanical Room
Outside of the computer room provide space for the heat ejection equipment and associated pumps, ...
Entrance Rooms
Class 3 and higher data centers shall have separate entrance rooms and the entrance room if separ...
Computer Room
The support equipment such as HVAC floor mounted air handlers, coolant distribution units, electr...
Planning Detail
The entry to the computer room from non-computer room spaces shall lead into a controlled space w...
General Paths of Access
All entries into the data center shall be secured. There should be a direct communication between...
Materials
The computer room shall be designed and built with new materials, which are durable, of superior ...
24/7 Operation of Data Center - Temperature and Relative Humidity Control
All Tier 3 and Tier 4 datacenter should have security personnel within the datacenter and securit...
Site Selection
The site should not have interfering elements. The below interfering elements should be eliminat...
Space Planning
Space planning is one of the key activities in the process of datacenter preparation. The size of...
Selection and Evaluation of the Site
This section emphasizes the requirements for evaluating and selecting a suitable site for the Dat...